Typical primary plan
An optional solution with a rated short-time breaking current of 1250A and a rated current of 25kA:
An optional solution with a rated short-time breaking current of 1250A and a rated current of 31.5kA:
An optional solution with a rated short-time breaking current of 2500A and a rated current of 31.5kA:
An optional solution with a rated short-time breaking current of 3150A and a rated current of 40kA:
Rated Parameters
S/N | Item | Unit | Parameter | ||||
1 | Rated voltage | kV | 24 | ||||
2 | Rated current | A | 630,1250,2500,3150,4000 | ||||
3 | Rated frequency | Hz | 50/60 | ||||
4 | Rated power frequency withstand voltage(1min) |
Phase-to-phase and Phase-to-earth |
kV | 65 | |||
Across isolating distance | kV | 79 | |||||
5 | Rated lightning impulse voltage (1.2/50ms) |
Phase-to-phase and Phase-to-earth |
kV | 125 | |||
Across isolating distance | kV | 145 | |||||
6 | Main circuit temperature rise | A | 1.1*Ir | ||||
7 | Rated short-time breaking current | kA | 25,31.5,40 | ||||
8 | Rated short-circuit closing current | kA | 63,80,100 | ||||
9 | Rated short circuit duration | s | 4 | ||||
10 | Rated short-time withstand current | kA | 25,31.5,40 | ||||
11 | Rated peak withstand current | kA | 63,80,100 | ||||
12 | Electrical life rating | / | E2 | ||||
13 | Dryair Rated pressure(20℃) | MPa | 0.07 | ||||
14 | Annual gas leakage rate | % | ≤0.01 | ||||
15 | Gas tank protection degree | / | IP67 | ||||
16 | Shell protection degree | / | IP4X | ||||
17 | Mechanical life of circuit breakers | times | 10000 | ||||
18 | Mechanical life of the disconnecting switch | times | 3000 | ||||
19 | Grounding switch mechanical life | times | 3000 |
Product Overview
The QCX E environmentally friendly gas-insulated metal-enclosed switchgear (C-GIS) is an environmentally friendly C-GIS product independently developed by Beijing Qingchang. The design adheres to environmentally friendly and green concepts, using dry air as the insulating gas. The voltage rating covers 10-35 kV, with currents ranging from 630 to 3150 A, and a rated breaking current of 25–40 kA. The equipment offers extremely high safety and reliability, ensuring the continuous and stable operation of power systems and the personal safety of operators. It also features a user-friendly interface, making it easy for on-site operators to use.
The QCX E-series switchgear adopts modern and innovative switchgear design concepts, with multiple functional modules available for selection. Commonly used functional modules include V, V-PT, V-G bus tie, and M metering, among others. Other modules can be customised according to the requirements of the primary system diagram when needed. These functional modules can be installed on-site.
Product Features
Flexible Combination
This product is designed with eco-friendly gas/SF6 universal solution, safe and reliable, meeting market demand.
Maintenance Free
The high-voltage conductor is completely sealed, with incoming and outgoing lines through insulating bushings, maintenance-free for the life cycle.
Miniaturization
Compact structure, reducing the footprint by about half compared to traditional switchgear.
Wide Application
It can be used in high-altitude and humid coastal areas.